Device control

Change a value or switch a device on or off from TCS-NET. It is off by default, permissioned, confirmed and logged.

Three layers of permission

Writing to a machine can make it move, so every layer must allow it:

  1. 01

    The control switch

    Off by default after installation. An administrator turns it on in Configuration.

  2. 02

    A writable tag

    Each tag must be marked writable (off by default) when it is added or edited.

  3. 03

    An administrator

    The signed-in user must be an administrator. Changing a device or a tag is also an administrator's job.

When you write a value

  • It always asks to confirm: the dialog names the device, the tag, the current value and the new one.
  • Safe values: an invalid value is refused and never silently adjusted to fit.
  • Read-back: after a write, TCS-NET reads again and tells you whether the device really holds the value.
  • A device that does not answer in time: the message says the value may have been applied and must be checked.
  • Every write is logged, success or failure, with who wrote, which tag, and the old and new value.

Protocols that can write

Writes work over Modbus TCP and RTU, Siemens S7, OPC UA, EtherNet/IP, MQTT and BACnet. SNMP and CANopen are read-only for now. Lua scripts cannot write to devices yet.